The purpose of the Nimbus control is to achieve the ideal flow rate for any circulator in your system. Flow rate is important. A boiler circulator that runs too slowly can overheat, while one that runs too quickly can reduce stratification in thermal storage tanks by mixing the hot and cold water.
Using the manual dip switch settings on the Nimbus, you can test different speeds to determine the best flow rate for transferring heat.
The default settings have all switches in the off position, as shown here.
Default dip switch settings
Using the dip switches, you can manually set the controller to a fixed speed. It can be configured in 1% increments between 27% and 100% output. Note: we have found that most circulators will not operate reliably below 40% when set on the Nimbus control.
Position for fixed speed control (27%)
Example of fixed speed at 50%
Using the Nimbus controller this way gives you a single user-defined speed for almost any circulator. Our experience has been primarily with TACO circulators (007, 0010, and 0014 models).
Using Nimbus for True Variable Speed with NFCS
Another way to use the Nimbus is with a NoFossil Control System (now called VESTA), also referred to as NFCS. The analog outputs (AO) in the left-hand column are the four outputs controlled by a 4-20 mA signal.
The benefit of using the Nimbus with the NFCS is that it can drive circulator speeds dynamically based on current heating system temperatures and rule sets. This gives greater control over the system and allows it to run at its optimum settings.
In this setup, the Nimbus is controlled by the NFCS via a 4-20 mA signal. The NFCS connects to each Nimbus controller through a signal wire that runs through a variable speed breakout box.
One of the first steps when setting up a variable speed controller to work with NFCS is to configure the jumper so it accepts a 4-20 mA signal.
Jumper is shown in correct position for 4-20 mA as used with NFCS.
Using the manual, you can determine the best settings for your system. The example below is configured for current control and is set to run at 60% if no signal is present. Where the manual refers to a “fan,” it applies to the circulator in our application.
A. Fan On / Fan Off Feature (switch #1): To turn the fan(s) off below the set idle speed (see Table 3), set switch #1 to the ON position. To keep the fans running at idle speed below the set idle speed, set switch #1 to the OFF position.
C. Control Signal Loss Options (switch #6): If the control signal is lost (less than 4 mA in I mode, or less than 2 VDC in V mode) and switch 6 is OFF, the fans will continue to idle or remain off. To send the fans to full speed if the control signal is lost, set switch 6 to the ON position.
If the NFCS is offline and not supplying 4-20 mA signals, the Nimbus can be configured to either run at one of four preselected idle speeds or run wide open, assuming the aquastat or other control switch is supplying line voltage to the Nimbus.
Connecting a variable speed control unit to the NFCS
Originally published: January 2010